IEC 60909-07 min read

Two Transformers in Parallel: What Happens to the Fault Level When the Bus Coupler Closes?

Part 4 of the short-circuit series. Each 1.6 MVA transformer gives 37.4 kA on its own. Closing the bus coupler raises the fault level to 67.5 kA — beyond the 50 kA switchboard.

Scenario

Supply250 MVA, 11 kV grid feeding two identical 1.6 MVA, 6 %, Dyn transformers T1 and T2
LV switchboardTwo sections A and B, each rated 50 kA, with a bus coupler between them

Step-by-step calculation

Step 1: Bus coupler open

Each section is fed by one transformer, exactly as in Part 1.

Step 2: Bus coupler closed — impedances in parallel

The two transformer impedances are now in parallel, but both are fed through the same grid impedance, so the current does not quite double.

Z = Z_Q + (KT × Z_T) / 2
Z = (0.0438 + j0.4378) + (0.5644 + j3.5678)/2 = 0.326 + j2.222 pu → |Z| = 2.246 pu
Ik″ = 1.05 × 144.34 / 2.246 = 67.49 kA

Step 3: Earth fault and peak with the coupler closed

Step 4: Options

Either keep the coupler open in normal service and interlock it so it can only close when one incomer is open (the common solution), or specify switchgear rated for the parallel fault level, or limit the current with a reactor or a fault-current limiter.

Result summary

CheckRequirementActualStatus
Coupler open≤ 50 kA37.41 kA✓ PASS
Coupler closed (paralleled)≤ 50 kA67.49 kA✗ FAIL
With the coupler closed the fault level is 67.5 kA (72.2 kA for an earth fault), well above the 50 kA rating. The transformers must not run in parallel unless the switchgear is rated for it; an interlock is the usual answer.

Key insight: Paralleling sources is one of the most common ways a fault level grows beyond the switchgear rating after commissioning — for example when a second transformer or a generator is added later.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open IEC 60909 Short-Circuit Calculator calculator →

Frequently asked questions

Is a short-time parallel during changeover acceptable?

Only if the switchgear is rated for the paralleled fault level, or the parallel period is so short and controlled that the user accepts the risk. Many specifications require the rating to cover it.

Why is the earth fault higher than the three-phase fault?

For Dyn transformers the zero-sequence impedance is close to the positive-sequence impedance and there is no grid zero-sequence path in series, so the single-phase fault can exceed the three-phase fault near the transformer.