Fault Current Propagation Through a Distribution Network

The classic "Base kVA Method" โ€” converts every element's %impedance to a common kVA base and accumulates it down a radial chain (source โ†’ transformer โ†’ cable โ†’ sub-panel) to estimate available fault current at each point.

Quick estimate. For a full study with several sources, motors, different voltage levels, earth faults and peak/breaking currents, use the IEC 60909 Short-Circuit Calculator.
AAJappsEngineering Calculation Report

Fault Current Propagation (Base kVA Method)

Base kVA Method โ€” scalar %Z approximation, see caveat below

Generated

For preliminary engineering use only โ€” always verify results against project-specific standards and a qualified engineer's review before use in a real design.

Base & system

kVA
kV
MVA

Series elements (source โ†’ load)

%Z atkVA
%Z atkVA

Network diagram

Visualisation only ยท not to scale

Source at the top, load at the bottom. The bar beside each bus shows its available fault current relative to the source.

Utility sourceIncoming bus โ€” 347.80 kA250.0 MVA ยท cumulative 0.40% ZTransformer (1000kVA, 6%Z)+6.00% Z at baseBus 1 โ€” 21.74 kA15.6 MVA ยท cumulative 6.40% ZCable to Sub-Panel+1.50% Z at baseBus 2 โ€” 17.61 kA12.7 MVA ยท cumulative 7.90% Z

Fault current down the network

Source %Z (at base)0.400%
At source / incoming347.80 kA (250.0 MVA)
Transformer (1000kVA, 6%Z)21.74 kA (15.6 MVA)
Cable to Sub-Panel17.61 kA (12.7 MVA)