Build a radial network — buses, utility sources, generators, motors, transformers, cables and bus ties — and the single-line diagram and the short-circuit current at every bus appear instantly: Ik″, peak, breaking, thermal, line-to-line and line-to-earth, plus minimum values. Several sources can feed the same bus. Calculated to IEC 60909-0 on a 100 MVA per-unit base; full step-by-step working is below and in the PDF report.
IEC 60909-0 (initial, peak, breaking and thermal short-circuit currents)
Generated
For preliminary engineering use only — always verify results against project-specific standards and a qualified engineer's review before use in a real design.
No saved scenarios yet. Build a network, give it a name and press “Save as new”.
Highest fault level: 0.4 kV LV Board at 39.58 kA (Ik″), peak 100.8 kA.
| Bus | Un (kV) | Ik″ 3-ph (kA) | ip (kA) | Ib (kA) | Ith (kA) | Ik″ L-L (kA) | Ik″ L-E (kA) | Ik″ min (kA) | Rating |
|---|---|---|---|---|---|---|---|---|---|
| 11 kV Switchboard | 11.0 | 14.20 | 40.17 | 13.88 | 14.44 | 12.30 | 14.50 | 14.04 | 25 kA ✓ |
| 0.4 kV LV Board | 0.400 | 39.58 | 100.77 | 39.58 | 39.99 | 34.28 | 40.34 | 34.41 | 50 kA ✓ |
| Motor Control Centre | 0.400 | 23.49 | 48.44 | 23.49 | 23.58 | 20.34 | 16.63 | 18.82 | 36 kA ✓ |
Maximum values use cmax with all sources and motors; “min” uses cmin, motors off and cables at 80 °C. “L-E” = line-to-earth; n/a means no zero-sequence path to earth.
Add or edit anything below — the diagram and tables above update immediately. Use “Apply typical values…” on any item to start from a realistic set of constants.
Each bus is a busbar at one nominal voltage. Sources and branches attach to buses.
Any number per bus. Generators and the utility feed the fault; motors add to the maximum fault current only.
Each branch joins two buses. For a transformer, the ‘from’ bus is the first-listed winding side (HV side by convention).
Every number above can be reproduced by hand from these steps. Impedances are shown in per unit on 100 MVA; the bus Thevenin impedance combines all sources, transformers and cables (series/parallel reduction).
Contributions to Ik″: Utility incomer 13.12 kA · Gen G1 1.01 kA · Motor M1 0.07 kA
Contributions to Ik″: Utility incomer 35.00 kA · Gen G1 2.70 kA · Motor M1 1.95 kA
Contributions to Ik″: Utility incomer 19.92 kA · Gen G1 1.54 kA · Motor M1 2.03 kA
| LV 100–1000 V, +6 % tolerance | cmax 1.05 / cmin 0.95 | Default for 230/400 V public networks. |
| LV 100–1000 V, +10 % tolerance | cmax 1.10 / cmin 0.95 | Use where the supply voltage may reach +10 %. |
| MV and HV > 1 kV | cmax 1.10 / cmin 1.00 | Applies to 3.3, 6.6, 11, 33, 132 kV etc. |
| R/X of source | 0.1 (HV), 0.3 (LV) | IEC: XQ = 0.995 ZQ when R = 0.1 X. Use the utility's X/R if known. |
| Typical Sk″ at 11 kV | 150 – 500 MVA | 8 – 26 kA. Ask the utility for the real value. |
| Typical Sk″ at 33 kV | 500 – 1500 MVA | Up to 25 – 31.5 kA switchgear. |
| Z0/Z1 of source | 1.0 (typical) | Depends on utility earthing; 0.5–3 possible. |
| uk, up to 630 kVA | 4 % | IEC 60076-5 / EN 50464 distribution range. |
| uk, 800 – 3150 kVA | 6 % | |
| uk, 5 – 40 MVA | 7.5 – 14 % | Check the nameplate; rises with rating and voltage. |
| KT = 0.95·cmax/(1+0.6·xT) | ≈ 0.93 – 1.0 | Applied to Z1 and Z0; not applied to power-station unit transformers. |
| Z0/Z1 | 0.85 – 1.0 | Dyn ≈ 1.0; 3-limb YNyn 0.8–1.0. |
| RG/Xd″ when UrG ≤ 1 kV | 0.15 | IEC 60909-0 cl. 3.6.1. |
| RG/Xd″ when UrG > 1 kV, SrG < 100 MVA | 0.07 | |
| RG/Xd″ when UrG > 1 kV, SrG ≥ 100 MVA | 0.05 | |
| xd″ | 12 – 20 % | Salient-pole 12–25 %; turbo 10–20 %. |
| x0 | ≈ 0.4 – 0.6 xd″ | Use the datasheet where available. |
| RM/XM, LV motor groups | 0.42 | IEC 60909-0 cl. 3.8 (includes connection cables). |
| RM/XM, MV motor < 1 MW per pole pair | 0.15 | |
| RM/XM, MV motor ≥ 1 MW per pole pair | 0.10 | |
| ILR/IrM | 5 – 7 | Locked-rotor to rated current. |
| Efficiency × cos φ | 0.80 – 0.90 | Used to get SrM = Pr/(η·cos φ). |
| Cu 3C XLPE 240 mm² LV | r 0.0754, x 0.078 Ω/km | r at 20 °C; code raises r to 80 °C (×1.24) for the minimum case. |
| Z0 of 3-core cable | r0 ≈ 4 r, x0 ≈ 3 x | Use manufacturer data for single-core/screen returns. |