Build the network once and get the arc-flash incident energy, boundary, PPE category and warning label for every bus. Fault currents come from the IEC 60909 short-circuit model, the arc duration from the protective device you describe, and the arc-flash result from the full IEEE 1584-2018 model (208 V – 15 kV) at both maximum and minimum fault current, including the reduced-arcing-current check. Includes a colour-coded single-line diagram, boundary and energy graphs, a what-if for faster clearing, printable NFPA 70E style labels and the step-by-step calculation.
IEEE 1584-2018 · IEC 60909-0 · NFPA 70E reference tables
Generated
For preliminary engineering use only — always verify results against project-specific standards and a qualified engineer's review before use in a real design.
No saved scenarios yet. Build a network, give it a name and press “Save as new”.
Highest incident energy: 0.4 kV LV Board at 21.2 cal/cm² (PPE Category 3), boundary 3.68 m.
| Bus | Voc (kV) | Ibf max / min (kA) | Iarc (kA) | Arc time (ms) | E (cal/cm²) | AFB (mm) | Work dist (mm) | PPE | With maintenance mode | Clear in ≤ (ms) for 8 cal/cm² |
|---|---|---|---|---|---|---|---|---|---|---|
| 11 kV Switchboard | 11.0 | 14.2 / 14.1 | 12.9 | 300 | 4.7 | 2182 | 914 | Cat 2 | – | met |
| 0.4 kV LV Board | 0.400 | 39.7 / 37.9 | 23.8 | 526 | 21.2 | 3676 | 610 | Cat 3 | 2.0 (50 ms) | 199 |
| Motor Control Centre | 0.400 | 23.0 / 20.3 | 16.0 | 100 | 2.5 | 730 | 457 | Cat 1 | – | met |
E is the higher of the average-arcing-current and reduced-arcing-current cases, at the worse of the maximum and minimum fault current. Arc time is the protective-device clearing time at the governing arcing current. Select a row for graphs and the label.
Vertical lines mark 8, 25 and 40 cal/cm² (PPE Category 2, 3 and 4 limits).
The incident energy is already at or below 8 cal/cm² (Category 2).
Category 1 clothing at the higher rating, with arc-rated balaclava and face shield or arc flash suit hood.
One label per bus, in the NFPA 70E / ANSI Z535 style. Print on adhesive label stock and attach to the equipment. Re-print after any change to the system.
The same editor as the IEC 60909 calculator. Add buses, sources, transformers, cables and ties; the diagram and fault levels follow.
Add or edit anything below — the diagram and tables above update immediately. Use “Apply typical values…” on any item to start from a realistic set of constants.
Each bus is a busbar at one nominal voltage. Sources and branches attach to buses.
Any number per bus. Generators and the utility feed the fault; motors add to the maximum fault current only.
Each branch joins two buses. For a transformer, the ‘from’ bus is the first-listed winding side (HV side by convention).
Equipment class, electrode configuration, enclosure, working distance, and the device that clears an arcing fault.
Each bus lists the inputs, intermediate values and final results so the study can be checked by hand against the equations of clause 4. The fault current itself comes from the IEC 60909 working on the Short Circuit page.
| Equipment | Gap (mm) | Enclosure H × W × D (mm) | Working distance (mm) |
|---|---|---|---|
| 15 kV switchgear | 152 | 1143 × 762 × 762 | 914.4 |
| 15 kV MCC | 152 | 914.4 × 914.4 × 914.4 | 914.4 |
| 5 kV switchgear | 104 | 914.4 × 914.4 × 914.4 | 914.4 |
| 5 kV MCC | 104 | 660.4 × 660.4 × 660.4 | 914.4 |
| Low-voltage switchgear | 32 | 508 × 508 × 508 | 609.6 |
| Shallow LV MCC / panelboard (≤ 203 mm deep) | 25 | 355.6 × 304.8 × 203.2 | 457.2 |
| Deep LV MCC / panelboard (> 203 mm deep) | 25 | 355.6 × 304.8 × 254 | 457.2 |
| Cable junction box | 13 | 355.6 × 304.8 × 203.2 | 457.2 |