IEC 60909-010 min read

Short Circuit Calculation Basics: MVA Method vs Per-Unit (IEC 60909) for a 1.6 MVA Transformer

Part 1 of the short-circuit series. The same LV board fault worked two ways — the quick MVA method and the IEC 60909 per-unit method — and why they differ by 7.6 %.

Scenario

Network250 MVA, 11 kV grid (R/X = 0.1) → 1.6 MVA, 11/0.4 kV Dyn transformer, uk = 6 %, Pk = 15 kW
FaultThree-phase bolted fault on the 0.4 kV LV board
LV tolerance+6 % (cmax = 1.05 at LV, 1.10 at 11 kV)

Step-by-step calculation

Step 1: Quick check: the MVA method

Each element is turned into its own short-circuit power and the powers are combined like resistors in parallel.

S_T = Sr / uk; 1/S = 1/S_grid + 1/S_T; Ik = S / (√3 × U)
S_T = 1.6 / 0.06 = 26.67 MVA; S = 1 / (1/250 + 1/26.67) = 24.10 MVA; Ik = 24.10 / (√3 × 0.4)
Ik ≈ 34.8 kA

Step 2: IEC 60909 — grid impedance in per unit (Sbase = 100 MVA)

Z_Q = c × Sbase / Sk″
Z_Q = 1.10 × 100 / 250 = 0.440 pu; with R/X = 0.1: Z_Q = 0.0438 + j0.4378 pu
Z_Q = 0.0438 + j0.4378 pu

Step 3: Transformer impedance and correction factor KT

ukr = Pk / Sr; ux = √(uk² − ukr²); KT = 0.95 × cmax / (1 + 0.6 × xT)
ukr = 15 kW / 1600 kVA = 0.9375 %; ux = 5.926 %; Z_T = (0.9375 + j5.926) % × 100/1.6 = 0.586 + j3.704 pu; KT = 0.95 × 1.05 / (1 + 0.6 × 0.05926) = 0.9632
KT × Z_T = 0.5644 + j3.5678 pu

Step 4: Total impedance and fault current

Ik″ = c × Ibase / |Z|, Ibase = Sbase / (√3 × Un)
Z = 0.6082 + j4.0056 pu, |Z| = 4.0515 pu; Ibase = 100 / (√3 × 0.4) = 144.34 kA; Ik″ = 1.05 × 144.34 / 4.0515
Ik″ = 37.41 kA

In ohms at 0.4 kV: Z = 0.000973 + j0.006409 Ω (Zbase = 0.4²/100 = 0.0016 Ω).

Step 5: Why the two answers differ

The MVA method ignores the voltage factor c and the transformer correction KT, and treats impedances as pure reactances. IEC 60909 deliberately uses cmax = 1.05 for LV with +6 % tolerance, giving the maximum current needed for equipment ratings. The MVA method is a good sense check, but the equipment duty should be taken from IEC 60909.

Result summary

CheckRequirementActualStatus
MVA methodSense check34.8 kA✓ PASS
IEC 60909 maximum Ik″Used for equipment rating37.41 kA✓ PASS
LV board rating≥ 37.41 kA50 kA✓ PASS
The IEC 60909 maximum three-phase fault current on the LV board is 37.41 kA, 7.6 % above the quick MVA-method estimate of 34.8 kA. A 50 kA board is adequate.

Key insight: Over 85 % of the impedance comes from the transformer. For LV boards fed by a transformer, the transformer impedance sets the fault level; the grid strength matters much less.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open IEC 60909 Short-Circuit Calculator calculator →

Frequently asked questions

Why is c = 1.10 used for the 11 kV grid but 1.05 at LV?

IEC 60909-0 Table 1 gives cmax = 1.10 above 1 kV, and 1.05 (or 1.10 with a +10 % tolerance) at low voltage. The grid impedance is calculated with the factor of its own network.

What is KT for?

It corrects the transformer impedance for the real operating conditions before the fault, so the equivalent voltage source method gives the right maximum current.