IEC 60909-08 min read

Short Circuit at an MCC 80 m From the Transformer: How Much Does the Cable Reduce It?

Part 2 of the short-circuit series. Adding an 80 m feeder cuts the fault level from 37.4 kA to 22.9 kA and changes the X/R ratio — which affects the peak current and equipment selection.

Scenario

Network250 MVA, 11 kV grid (R/X = 0.1) → 1.6 MVA, 11/0.4 kV Dyn transformer, uk = 6 %, Pk = 15 kW
Feeder2 × 185 mm² Cu cables in parallel, 80 m; r = 0.0991 Ω/km, x = 0.0739 Ω/km per cable
FaultThree-phase and line-to-earth faults at the MCC

Step-by-step calculation

Step 1: Impedance at the LV board (from Part 1)

Step 2: Cable impedance

Z_c = (r + jx) × L / n
Z_c = (0.0991 + j0.0739) × 0.08 / 2
Z_c = 0.003964 + j0.002956 Ω

Step 3: Fault current at the MCC

Ik″ = c × Un / (√3 × |Z|)
Z = 0.004937 + j0.009365 Ω, |Z| = 0.010587 Ω; Ik″ = 1.05 × 400 / (√3 × 0.010587)
Ik″ = 22.90 kA

Step 4: Peak factor from the new R/X

κ = 1.02 + 0.98 × e^(−3R/X); ip = κ × √2 × Ik″
R/X = 0.527; κ = 1.02 + 0.98 × e^(−1.581) = 1.222; ip = 1.222 × 1.414 × 22.90
ip = 39.57 kA (at the board: κ = 1.641, ip = 86.8 kA)

Step 5: Line-to-earth fault

The calculator also solves the zero-sequence network (transformer Dyn earthed at the star point, cable zero-sequence impedance about 4 × the positive-sequence).

Result summary

CheckRequirementActualStatus
MCC three-phase Ik″≤ MCC rating 36 kA22.90 kA✓ PASS
MCC peak ip≤ making capacity39.6 kA✓ PASS
The 80 m feeder reduces the fault level from 37.41 kA at the board to 22.90 kA at the MCC, and the peak from 86.8 kA to 39.6 kA because the cable raises the R/X ratio.

Key insight: A short LV cable has as much impedance as the transformer. Equipment far from the transformer can often use lower-rated devices, but the minimum fault current (for protection) falls too — see Part 5.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open IEC 60909 Short-Circuit Calculator calculator →

Frequently asked questions

Should I use the cable resistance at 20 °C or at operating temperature?

For maximum fault current IEC 60909 uses 20 °C (lower resistance, higher current). For the minimum fault current it uses the resistance at the end of the fault, typically 80 °C.

Why does the peak drop more than the r.m.s. current?

Cable resistance damps the DC offset. A higher R/X gives a lower peak factor κ.