IEC 60909-09 min read

Minimum Earth Fault Current and the c-Factor: Will the Breaker Trip Instantaneously?

Part 5 of the short-circuit series. Maximum currents size equipment; minimum currents prove the protection works. At a DB 150 m away the minimum earth fault is 2.85 kA — too low for a 250 A breaker set at 10 × In.

Scenario

Network250 MVA, 11 kV grid (R/X = 0.1) → 1.6 MVA, 11/0.4 kV Dyn transformer, uk = 6 %, Pk = 15 kW
Feeder4-core 95 mm² Cu, 150 m; r = 0.193, x = 0.0779 Ω/km; r0 = 0.772, x0 = 0.234 Ω/km
Protection250 A MCCB at the LV board, instantaneous setting 10 × In, tolerance ±20 %

Step-by-step calculation

Step 1: Maximum fault currents at the DB

Step 2: Earth fault formula

Ik1 = √3 × c × Un / |2Z1 + Z0|
Z1 = 0.0299 + j0.0181 Ω; Z0 = 0.1167 + j0.0408 Ω (transformer + cable); |2Z1 + Z0| = 0.1926 Ω; Ik1 = √3 × 1.05 × 400 / 0.1926
Ik1 max = 3.78 kA

Step 3: Minimum case

IEC 60909 uses cmin = 0.95 at LV, leaves motors out and takes cable resistance at the end of the fault (×1.24 for copper at 80 °C).

Step 4: Check the instantaneous trip

Ii,max = setting × In × (1 + tolerance)
10 × 250 × 1.2 = 3,000 A > 2,845 A
Instantaneous operation is not guaranteed

The fault would then be cleared by the slower long-time element, which may exceed the disconnection time required by IEC 60364-4-41.

Step 5: Fix

Result summary

CheckRequirementActualStatus
Ik1 min vs 10 × In upper limitIk1 min > 3,000 A2,845 A✗ FAIL
Ik1 min vs 8 × In upper limitIk1 min > 2,400 A2,845 A✓ PASS
The minimum earth fault at the DB is 2.85 kA. A 250 A breaker at 10 × In might not trip instantaneously (upper limit 3.0 kA); reducing the setting to 8 × In (upper limit 2.4 kA) restores reliable fast clearing.

Key insight: Always calculate two values at every bus: the maximum current for equipment ratings and the minimum current for protection sensitivity. Long cables affect the minimum far more than the maximum.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open IEC 60909 Short-Circuit Calculator calculator →

Frequently asked questions

Why is the earth fault so much lower than the three-phase fault here?

The cable's zero-sequence impedance (including the return path) is about four times its positive-sequence impedance, and the cable dominates the loop at 150 m.

What else can fix a low minimum fault current?

A larger cable or a separate protective conductor, an RCD or earth-fault relay, or a breaker with an electronic trip unit and earth-fault (G) protection.