How duty type, ambient temperature and altitude turn a 65 A motor into a 96 A drive requirement — and why a 96 A drive is not quite enough.
| Motor | 400 V, full-load current 65 A |
| Load | Conveyor — constant torque (heavy duty) |
| Design margin | 10% |
| Site | 50 °C ambient, 1,500 m altitude |
| Candidate drive | 400 V, 96 A rated output |
A constant-torque load needs the drive's heavy-duty rating, which is roughly 85–87% of its normal-duty rating, so the requirement is raised by about 1.15 when comparing against normal-duty catalogue currents.
| Check | Requirement | Actual | Status |
|---|---|---|---|
| Drive voltage rating | ≥ 400 V | 400 V | ✓ PASS |
| Drive current rating | ≥ 96.2 A | 96 A | ✗ FAIL |
Key insight: On a hot, high site a drive can need nearly 50% more rated current than the motor's FLA. Sizing on motor kW alone would have picked a drive about a third too small.
Every input in this example is editable in the live calculator — no signup needed.
Open VFD Sizing Calculator calculator →No. They are common screening figures. Drive manufacturers publish their own derating curves, which take priority for the final selection.