Motor Calculator

NEC Article 430 (FLC tables, branch-circuit/OCPD/overload/disconnect sizing) or IEC general method β€” standalone, independent of any protection-relay motor tab.

AAJappsEngineering Calculation Report

Motor Calculator

NEC Article 430, IEC general method

Generated

For preliminary engineering use only β€” always verify results against project-specific standards and a qualified engineer's review before use in a real design.

FLC & branch-circuit sizing

Starting method & voltage-dip check

A
V
kVA
%

Multi-motor feeder sizing (NEC 430 Part V)

FLC & branch-circuit result

Full-Load Current (FLC)34.0 A
Branch-Circuit Min. Ampacity42.5 A
Max Branch-Circuit OCPD60 A (or 70 A under the 430.52(C)(1)(b) exception)
Overload / Disconnect Setting39.1 A (disc. 39.1 A)

Starting & voltage-dip result

Effective Starting Current180.0 A
Starting kVA143.41 kVA
Calculated Voltage Dip2.788% (limit 15%) βœ“

Multi-motor feeder result

Largest MotorLargest Motor
Feeder Min. Ampacity49.0 A
Feeder OCPD64 A