VFD Sizing Calculator

Recommends the minimum VFD rated output current needed for a motor, accounting for duty type (Variable vs Constant Torque), ambient temperature and altitude derating — before you shop for a specific drive.

Motor

A
V

Application

%

Installation conditions

Candidate VFD (optional check)

A
V

VFD sizing result

Duty multiplier1.00
Temperature factor1.00
Altitude factor1.00
Required output current71.5 A
Minimum VFD rated current71.5 A

How to size a VFD

Size a variable frequency drive on the motor's full-load current, not its kW, because drive ratings are thermal current limits. Choose the duty rating to match the load: variable torque (pumps and fans, about 110% overload for 60 s) or constant torque (conveyors, hoists, positive-displacement pumps, about 150% overload for 60 s).

Derate the drive above about 40 °C ambient and 1,000 m altitude, and allow a margin for motor nameplate tolerance and future load. The calculator gives the minimum drive current and checks a candidate drive's current and voltage.

Frequently asked questions

Can I size a VFD by kW?

Only as a first guess. Motors of the same kW can have different full-load currents, especially at low speed or high pole numbers, so always check the drive's output current against the motor nameplate FLA.

How much should a VFD be derated for temperature and altitude?

A common screening figure is about 1% per °C above 40 °C and 1% per 100 m above 1,000 m, but drive manufacturers publish their own curves, which take priority.

For preliminary engineering use. Results must be checked by a qualified engineer against the project's standards. How results are checked · Terms & disclaimer · Build 5da9168 · 2026-11-13