Worked Example: Soft Starter Selection for a 140 A Motor at 50 °C, 1500 m and 12 Starts per Hour

A 160 A soft starter looks big enough for a 140 A motor until ambient, altitude and starting duty are applied. How the derated capacity is worked out and which size passes.

Scenario

Motor75 kW, 400 V, full-load current 140 A
SiteAmbient 50 °C, altitude 1500 m
Duty12 starts per hour
Candidate soft starters160 A and 200 A, both rated 400 V

The derating rates used (1% per °C above 40 °C, 1% per 100 m above 1000 m, and a starts-per-hour factor) are typical manufacturer figures. The chosen manufacturer's own derating curves take precedence.

Step-by-step calculation

Step 1: Ambient temperature factor

k_T = 1 − 0.01 × (T − 40)
k_T = 1 − 0.01 × (50 − 40)
k_T = 0.90

Step 2: Altitude factor

k_A = 1 − 0.01 × (h − 1000) / 100
k_A = 1 − 0.01 × 500 / 100
k_A = 0.95

Step 3: Starting duty factor

11 to 20 starts per hour reduces the thermal capacity available for running current.

Step 4: Derated capacity of the 160 A unit

I_derated = I_rated × k_T × k_A × k_D
160 × 0.90 × 0.95 × 0.90
123.1 A < 140 A — not adequate

Step 5: Derated capacity of the 200 A unit

Result summary

CheckRequirementActualStatus
Voltage rating≥ 400 V400 V✓ PASS
160 A unit, derated≥ 140 A123.1 A✗ FAIL
200 A unit, derated≥ 140 A153.9 A✓ PASS
The 160 A soft starter is only good for 123.1 A at this site and duty, so the 200 A unit (153.9 A derated) is required.

Key insight: The three derating factors multiply. Each looks small on its own, but together they remove 23% of the rating here.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open Soft Starter Sizing Calculator calculator →

Frequently asked questions

Does a bypass contactor change the sizing?

An internally or externally bypassed soft starter carries running current through the contactor, so many manufacturers allow higher ratings or more starts. Use the bypassed rating tables in that case.

Why do more starts per hour reduce the rating?

Each start heats the thyristors with several times rated current. More starts leave less time to cool, so less continuous current can be carried.