t = J·ω / T_acc7 min read

Worked Example: Run-Up Time of a 90 kW Fan With a High-Inertia Impeller

How long a direct-on-line 90 kW motor takes to bring a large fan up to speed, and why the answer must be compared with the motor's locked-rotor withstand time.

Scenario

Motor90 kW, 4-pole, rated speed 1485 rpm, direct-on-line start
InertiaMotor rotor 1.2 kg·m² + fan impeller 45 kg·m² (direct drive) = 46.2 kg·m²
Average motor torque during run-up≈ 1.4 × rated torque (from the motor's speed–torque curve)
Average fan load torque during run-up≈ 174 N·m (fan torque rises with speed², averaged over the run-up)

Step-by-step calculation

Step 1: Rated torque of the motor

Tn = 9550 × P / n
Tn = 9550 × 90 / 1485
Tn = 578.8 N·m

Step 2: Average net accelerating torque

T_acc = T_motor,avg − T_load,avg
T_acc = 1.4 × 578.8 − 174 = 810 − 174
T_acc ≈ 636 N·m

The average is taken over the whole run-up. With the actual motor and load curves, a step-by-step integration gives a more exact result; the average-torque method is the usual first check.

Step 3: Target angular velocity

ω = 2π × n / 60
ω = 2π × 1485 / 60
ω = 155.5 rad/s

Step 4: Acceleration time

t = J × ω / T_acc
t = 46.2 × 155.5 / 636
t = 11.3 s

Step 5: Compare with the motor's locked-rotor withstand

During run-up the motor draws close to its starting current, so the run-up time must be safely shorter than the motor's permissible locked-rotor (stall) time, from the motor data sheet. A common practice is to require the run-up time to be no more than about 80% of the hot stall time, and to set the motor protection between the two.

Result summary

CheckRequirementActualStatus
Acceleration timeCalculated11.3 s (classed as a slow start)✓ PASS
Margin to stall time (example: 15 s hot stall time)t ≤ 0.8 × 15 = 12 s11.3 s — only just within✓ PASS
The fan takes about 11.3 s to reach speed. With a typical hot stall time of around 15 s, the margin is small, so the overload protection setting must be checked carefully, or a larger motor, a high-inertia motor design, or a soft or VFD start considered.

Key insight: Run-up time grows in direct proportion to inertia. A heavy fan impeller can make the start several times longer than the same motor driving a pump, even when the steady-state power is identical.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open Motor Acceleration Time Calculator calculator →

Frequently asked questions

How do I refer load inertia through a belt or gearbox?

Multiply the load inertia by the square of the speed ratio (load speed ÷ motor speed) before adding it to the motor inertia.

Does reduced starting voltage change the run-up time?

Yes. Motor torque falls roughly with the square of the voltage, so a 20% voltage dip during starting cuts torque by about 36% and lengthens the run-up.