IEC 60599:2022 / IEEE C57.104-20198 min read

Worked Example: Diagnosing a Low-Energy Discharge (D1) from a DGA Sample — IEC 60599 Ratios and Duval Triangle 1

Transformer TX-204 in the analyzer's demonstration fleet: acetylene has more than doubled in six months. Ratios, Duval coordinates, IEEE C57.104 status and what to do next.

Scenario

TransformerTX-204, 220/132 kV, 160 MVA, OFAF, sealed, mineral oil, built 2014
Latest sample (ppm)H2 210, CH4 70, C2H6 18, C2H4 55, C2H2 140, CO 360, CO2 2 800
TrendTDCG 424 → 607 → 853 ppm over two years; C2H2 rising 0.40 ppm/day

Open the DGA Analyzer and click TX-204 in the fleet to follow along.

Step-by-step calculation

Step 1: IEC 60599 gas ratios

RatioValueD1 range (Table 1)
C2H2/C2H4140/55 = 2.55> 1
CH4/H270/210 = 0.330.1 – 0.5
C2H4/C2H655/18 = 3.06> 1

Step 2: Duval Triangle 1

%gas = gas / (CH4 + C2H4 + C2H2) × 100
Sum = 70 + 55 + 140 = 265 ppm → CH4 26 %, C2H4 21 %, C2H2 53 %
Zone D1 (C2H4 < 23 %, C2H2 > 13 %)

Step 3: Other methods

Rogers ratios and Duval Pentagon 1 point to D2 (high-energy arcing); Pentagon 2 to D1. The analyzer weighs the methods and reports D1 with 42 % confidence, D2 29 % as the next candidate.

Step 4: Is it serious? IEEE C57.104-2019

Acetylene is at more than 5 × the Table 2 limit and H2, C2H4 and C2H2 all show significant increases between samples.

Step 5: Paper involvement

CO2/CO
2 800 / 360
7.8 — inside the normal 3–10 band: no evidence that paper is involved

Result summary

CheckRequirementActualStatus
IEC 60599 fault typeTable 1D1 — low-energy discharge✗ FAIL
Duval Triangle 1ZoneD1✗ FAIL
IEEE C57.104 statusStatus 1 = normalStatus 3 — Extreme✗ FAIL
Paper involvement (CO2/CO)3 – 107.8✓ PASS
TX-204 shows a low-energy discharge (D1) — sparking or tracking — with acetylene rising quickly enough for IEEE Status 3. Re-sample within days to confirm, then shorten the sampling interval and plan an internal inspection; check tap-changer leakage if the unit has a communicating OLTC.

Key insight: Methods disagree near the D1/D2 boundary. The rate of increase of acetylene, not the exact zone, decides how urgent the response is.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open DGA Analyzer (Transformer Oil) calculator →

Frequently asked questions

Why do Rogers and Pentagon 1 say D2?

D1 and D2 sit next to each other on every method. A sample near the boundary can fall on either side; the analyzer shows all methods so you can see the spread.

Could this be from the tap changer?

Yes, if the OLTC compartment leaks into the main tank. IEC 60599 §5.7 flags C2H2/H2 above about 2–3; here it is 0.67, which does not indicate contamination.