Transformer Sizer

Sizes a new transformer — or an N-1 redundant group — from connected load, growth/safety margins, ambient + altitude derating (IEC 60076-1/2/11-aligned reference conditions), and standard ANSI/IEEE or IEC preferred kVA ratings. For analyzing losses/efficiency of an existing transformer, see the Generator & Transformer Analysis calculator instead. Fully

AAJappsEngineering Calculation Report

Transformer Sizer

IEC 60076-1/2/11

Generated

For preliminary engineering use only — always verify results against project-specific standards and a qualified engineer's review before use in a real design.

Connected load

kW

Margins & derating

%
%
°C
m

Standard sizes & redundancy

With N total units, any (Nāˆ’1) must be able to carry the full design load alone — N=2 (the common 1-for-1 redundant pair) sizes each unit for 100% of the load; N=1 means no redundancy. Ambient/altitude derating rates above the IEC reference points are commonly published engineering rules of thumb — always confirm against the manufacturer's thermal/altitude rating curve for a final selection.

Sizing result

Design Load888.9 kVA
Margined Load1124.4 kVA
Ambient Derate Factor0.9375
Altitude Derate Factor1.0000
Combined Derate Factor0.9375
Effective Required Capacity1199.4 kVA
Per-Unit Required (Ć·1)1199.4 kVA
Recommended Standard Size1500 kVA per unit
Total Installed Capacity3,000 kVA