Sizes a new transformer \u2014 or an N-1 redundant group \u2014 from connected load, growth and safety margins, ambient and altitude derating, and standard kVA ratings. Distinct from the Generator & Transformer Analysis calculator's Transformer tab, which analyzes an existing unit's losses/efficiency from test data rather than sizing a new one from load.
Standards followed
IEC 60076-1 §4.2 (reference conditions)IEC 60076-2 §5.1/§6.3.2 (temperature rise & altitude)IEC 60076-11 (dry-type altitude)IEC 60076-1 R10 preferred sizesANSI/IEEE C57.12.00-style ratings
What it can do
- Sizes from kW+PF or direct kVA, with growth and safety margins.
- Ambient derating above the IEC 40°C reference and altitude derating above the IEC 1000m reference, with separate rates for naturally- vs. forced-cooled types.
- N-1 redundant group sizing ā any (Nā1) of N identical units carries the full load.
- Rounds to either ANSI/IEEE or IEC 60076-1 preferred standard kVA sizes.
Example problem
Size an N-1 redundant pair (N=2) of transformers for an 800kW, 0.9 PF load, with 15% growth margin, 10% safety margin, 45°C ambient, and 1000m altitude.
- Design load = 800 / 0.9 = 888.9 kVA.
- Margined load = 888.9 Ć 1.15 Ć 1.10 = 1124.4 kVA.
- Ambient derate factor = 1 ā (45ā40)Ć1.25% = 0.9375 (5°C above the 40°C IEC reference).
- Altitude derate factor = 1.0 (at the 1000m reference, no altitude derating applies).
- Effective required capacity = 1124.4 / 0.9375 = 1199.4 kVA.
- With N=2, any 1 of 2 units must carry the full 1199.4 kVA alone ā per-unit requirement = 1199.4 kVA.
- Round up to the nearest standard ANSI size ā 1500 kVA per unit (3000 kVA total installed).
1500 kVA per unit, 3000 kVA total installed.
Want the full step-by-step version?
The 40\u00b0C ambient and 1000m altitude reference points are directly from IEC 60076-1/2, but the specific derating rates (%/\u00b0C, %/100m) are commonly published engineering rules of thumb, not literal standard values \u2014 always confirm against the manufacturer's own thermal/altitude rating curve.