Distance Protection Setting Assistant

Proposed zone reaches and times for a line distance relay from the line and network data: residual compensation k0, zones 1–3 and a reverse zone in primary and secondary ohms, resistive reaches limited by load, and checks for load encroachment, source impedance ratio and short lines.

Line and network data

Proposed zones — line 16.32 Ω ∠ 78.7°

ZoneReach primaryReach secondaryR earth / phase (prim.)R earth / phase (sec.)Time
Zone 1
80 % of the protected line (instantaneous; margin for CT/VT, line data and relay errors)
13.05 Ω8.70 Ω24.0 / 3.6 Ω16.0 / 2.4 Ω0 s
Zone 2
≥ 120 % of the line, ≤ line + 50 % of the shortest adjacent line
21.42 Ω14.28 Ω24.0 / 3.6 Ω16.0 / 2.4 Ω0.35 s
Zone 3
120 % of line + longest adjacent line (remote back-up)
48.96 Ω32.64 Ω24.0 / 3.6 Ω16.0 / 2.4 Ω0.9 s
Zone 4 (reverse)
15 % reverse, for busbar back-up / blocking schemes
2.45 Ω1.63 Ω24.0 / 3.6 Ω16.0 / 2.4 Ω1.2 s

Minimum load impedance at 0.9 pu: 94.1 Ω; resistive reach limit 65.2 Ω · SIR 1.23.

Checks

  • NoteResidual compensation k0 = (Z0 − Z1) / 3Z1 = 0.668 ∠ -0.7°; line angle 78.7°. Secondary ohms = primary × CT ratio / VT ratio = primary × 0.6667.

Characteristics (earth-fault resistive reach, primary Ω)

RXZone 1Zone 2Zone 3Zone 4R
Tool guide · know before you use

What this tool is, how it works and how far to trust it

A setting assistant that proposes distance relay zone reaches, times and resistive reaches for a line from the line and network data.

Read this before relying on a result. Every method, formula, assumption and limit is stated here, so you can check the answer yourself instead of accepting it blindly.

What it can do

  • Compute the line impedance, angle and residual compensation k0 from R1, X1, R0, X0 and the length.
  • Propose zone 1, zone 2, zone 3 and a reverse zone in primary and secondary ohms with their times and the rule behind each.
  • Propose earth-fault and phase-fault resistive reaches and limit them by the minimum load impedance at the load angle.
  • Warn for load encroachment, source impedance ratio above 4 and short lines; sketch the quadrilateral characteristics.

Why you need it

  • Each zone rule has a limit set by the adjacent lines, the load and the source; laying them out together keeps the setting sheet consistent.
  • Primary and secondary ohms side by side avoid the most common setting error — a wrong CT/VT ratio conversion.

Understand this first

  • Zone 1 under-reaches the remote end (80 %) so it can trip instantly without overreaching for errors in line data, CTs and VTs.
  • Zone 2 covers the rest of the line with a delay (0.3–0.4 s) and must not reach beyond zone 1 of the shortest adjacent line.
  • Zone 3 backs up the adjacent lines (0.8–1.0 s) and is the zone most at risk of tripping on heavy load.
  • Secondary ohms = primary ohms × CT ratio / VT ratio.

What you need before you start

  • Line R1, X1, R0, X0 per km and length; the shortest and longest adjacent lines.
  • CT and VT ratios, system voltage, maximum load and load angle, source impedance, fault resistances to cover.
  • A current browser (Chrome, Edge, Firefox or Safari). Nothing is installed and your data is never uploaded; it is processed on your own computer.

How to use it

  • Enter the line and network data (the defaults show the worked example).
  • Read the proposed zones and the checks; adjust the resistances or the reach rules if a check fails.
  • Transfer the values to the relay's setting sheet, using the relay's own settings for k0 and the characteristic.

What you get

  • A table of zones with reach in primary and secondary ohms, earth and phase resistive reaches and times.
  • Load impedance, resistive reach limit, SIR and checks; a quadrilateral sketch.

How to read the results

  • Zone 3 reaches into the load area: reduce the resistive reach or use load encroachment blinders.
  • SIR above 4: zone 1 accuracy suffers on a weak source — consider a lower zone 1 reach or a teleprotection scheme.
  • Very short line: zone 1 may be impractical; use line differential or a permissive scheme.

Technical basis

  • IEC 60255-121, IEEE C37.113 and common utility practice (80 % / 120 % / 0.3–0.4 s / 0.8–1.0 s).
  • Zone 2 = max(1.2 ZL, ZL + 0.5 Zadj,short), capped at ZL + 0.64 Zadj,short; zone 3 = 1.2 (ZL + Zadj,long); reverse 15 %; resistive reach 1.2 × 2 Rf (earth), 1.2 × Rarc (phase), ≤ 0.8 × Zload,min × cos(load angle).

Limits: when not to rely on it

  • A starting point, not the setting study: infeed, mutual coupling, series compensation, power swing and teleprotection schemes need the full study.
  • Relay-specific characteristics, k0 formats and angle conventions differ — follow the manufacturer's manual.

For preliminary engineering use. Results must be checked by a qualified engineer against the project's standards. How results are checked · Terms & disclaimer · Privacy · Build 7cfcbe2 · 2026-11-14