Distance Protection Setting Assistant
Proposed zone reaches and times for a line distance relay from the line and network data: residual compensation k0, zones 1–3 and a reverse zone in primary and secondary ohms, resistive reaches limited by load, and checks for load encroachment, source impedance ratio and short lines.
Line and network data
Proposed zones — line 16.32 Ω ∠ 78.7°
| Zone | Reach primary | Reach secondary | R earth / phase (prim.) | R earth / phase (sec.) | Time |
|---|---|---|---|---|---|
| Zone 1 80 % of the protected line (instantaneous; margin for CT/VT, line data and relay errors) | 13.05 Ω | 8.70 Ω | 24.0 / 3.6 Ω | 16.0 / 2.4 Ω | 0 s |
| Zone 2 ≥ 120 % of the line, ≤ line + 50 % of the shortest adjacent line | 21.42 Ω | 14.28 Ω | 24.0 / 3.6 Ω | 16.0 / 2.4 Ω | 0.35 s |
| Zone 3 120 % of line + longest adjacent line (remote back-up) | 48.96 Ω | 32.64 Ω | 24.0 / 3.6 Ω | 16.0 / 2.4 Ω | 0.9 s |
| Zone 4 (reverse) 15 % reverse, for busbar back-up / blocking schemes | 2.45 Ω | 1.63 Ω | 24.0 / 3.6 Ω | 16.0 / 2.4 Ω | 1.2 s |
Minimum load impedance at 0.9 pu: 94.1 Ω; resistive reach limit 65.2 Ω · SIR 1.23.
Checks
- NoteResidual compensation k0 = (Z0 − Z1) / 3Z1 = 0.668 ∠ -0.7°; line angle 78.7°. Secondary ohms = primary × CT ratio / VT ratio = primary × 0.6667.
Characteristics (earth-fault resistive reach, primary Ω)
What this tool is, how it works and how far to trust it
A setting assistant that proposes distance relay zone reaches, times and resistive reaches for a line from the line and network data.
Read this before relying on a result. Every method, formula, assumption and limit is stated here, so you can check the answer yourself instead of accepting it blindly.
What it can do
- Compute the line impedance, angle and residual compensation k0 from R1, X1, R0, X0 and the length.
- Propose zone 1, zone 2, zone 3 and a reverse zone in primary and secondary ohms with their times and the rule behind each.
- Propose earth-fault and phase-fault resistive reaches and limit them by the minimum load impedance at the load angle.
- Warn for load encroachment, source impedance ratio above 4 and short lines; sketch the quadrilateral characteristics.
Why you need it
- Each zone rule has a limit set by the adjacent lines, the load and the source; laying them out together keeps the setting sheet consistent.
- Primary and secondary ohms side by side avoid the most common setting error — a wrong CT/VT ratio conversion.
Understand this first
- Zone 1 under-reaches the remote end (80 %) so it can trip instantly without overreaching for errors in line data, CTs and VTs.
- Zone 2 covers the rest of the line with a delay (0.3–0.4 s) and must not reach beyond zone 1 of the shortest adjacent line.
- Zone 3 backs up the adjacent lines (0.8–1.0 s) and is the zone most at risk of tripping on heavy load.
- Secondary ohms = primary ohms × CT ratio / VT ratio.
What you need before you start
- Line R1, X1, R0, X0 per km and length; the shortest and longest adjacent lines.
- CT and VT ratios, system voltage, maximum load and load angle, source impedance, fault resistances to cover.
- A current browser (Chrome, Edge, Firefox or Safari). Nothing is installed and your data is never uploaded; it is processed on your own computer.
How to use it
- Enter the line and network data (the defaults show the worked example).
- Read the proposed zones and the checks; adjust the resistances or the reach rules if a check fails.
- Transfer the values to the relay's setting sheet, using the relay's own settings for k0 and the characteristic.
What you get
- A table of zones with reach in primary and secondary ohms, earth and phase resistive reaches and times.
- Load impedance, resistive reach limit, SIR and checks; a quadrilateral sketch.
How to read the results
- Zone 3 reaches into the load area: reduce the resistive reach or use load encroachment blinders.
- SIR above 4: zone 1 accuracy suffers on a weak source — consider a lower zone 1 reach or a teleprotection scheme.
- Very short line: zone 1 may be impractical; use line differential or a permissive scheme.
Technical basis
- IEC 60255-121, IEEE C37.113 and common utility practice (80 % / 120 % / 0.3–0.4 s / 0.8–1.0 s).
- Zone 2 = max(1.2 ZL, ZL + 0.5 Zadj,short), capped at ZL + 0.64 Zadj,short; zone 3 = 1.2 (ZL + Zadj,long); reverse 15 %; resistive reach 1.2 × 2 Rf (earth), 1.2 × Rarc (phase), ≤ 0.8 × Zload,min × cos(load angle).
Limits: when not to rely on it
- A starting point, not the setting study: infeed, mutual coupling, series compensation, power swing and teleprotection schemes need the full study.
- Relay-specific characteristics, k0 formats and angle conventions differ — follow the manufacturer's manual.
For preliminary engineering use. Results must be checked by a qualified engineer against the project's standards. How results are checked · Terms & disclaimer · Privacy · Build 7cfcbe2 · 2026-11-14