IEEE 81 / BS 74307 min read

Soil Resistivity From a Wenner Test: Turning Readings Into a Design Value

Part 1 of the earthing series. Five Wenner readings at increasing spacings, converted to apparent resistivity — and what the trend says about the soil layers.

Scenario

TestWenner four-pin method, equal spacing a, probes driven to a small depth compared with a
Readingsa = 1, 2, 4, 8, 16 m; R = 15.0, 6.9, 2.9, 1.2, 0.55 Ω

Step-by-step calculation

Step 1: Apparent resistivity

Valid when the probe depth is small compared with the spacing.

ρa = 2π × a × R

Step 2: Work through each spacing

Spacing a (m)R (Ω)ρa = 2πaR (Ω·m)
115.094.2
26.986.7
42.972.9
81.260.3
160.5555.3

Step 3: Read the trend

Resistivity falls as spacing rises, and the spacing roughly indicates the depth being sampled. The soil is therefore more conductive at depth: a drier top layer of about 95 Ω·m over a wetter lower layer of about 55 Ω·m.

Step 4: Choose a design value

For a grid about 40 m across, the spacings comparable to the grid size (8–16 m) matter most for grid resistance, while the top layer governs touch voltage near the surface. A single uniform value of about 95 Ω·m (the top layer) is conservative for touch and step voltages; a two-layer model gives a more economical design.

Result summary

CheckRequirementActualStatus
Apparent resistivity at 1 m—94.2 Ω·m✓ PASS
Apparent resistivity at 16 m—55.3 Ω·m✓ PASS
The readings give 94 Ω·m near the surface falling to 55 Ω·m at depth. Use about 95 Ω·m as a conservative uniform value, or model the soil as two layers when the design margin is tight.

Key insight: Never design from a single reading. Measure along at least two directions and several spacings; the trend with spacing is as important as the values.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open Earthing Grid Design (IEEE 80) calculator →

Frequently asked questions

When should the test be done?

Ideally in dry conditions, which give the highest (worst-case) resistivity, and away from buried metal pipes or cables that distort the readings.

What if resistivity rises with depth?

Then deep rods help less and a larger horizontal grid is usually more effective.