NEC Article 220 (Parts III and IV)7 min read

Worked Example: NEC 220 Dwelling Service Size — Standard vs Optional Method

A 2,000 ft² house works out at 150 A by the standard method but 125 A by the optional method — here is where the difference comes from.

Scenario

Floor area2,000 ft²
Small-appliance and laundry circuits2 × 1,500 VA and 1 × 1,500 VA
Other fixed appliances3 appliances totalling 4,500 VA
Range and dryer10 kW range, 5,000 VA dryer
HVAC4,800 VA cooling, 10,000 VA heat pump heating (larger of the two used)
Supply240 V single-phase

Step-by-step calculation

Step 1: Standard method: general loads with the Table 220.42 demand factors

Lighting 3 VA/ft² × 2,000 = 6,000 VA; + 4,500 VA small appliance and laundry = 10,500 VA
3,000 × 100% + 7,500 × 35%
5,625 VA

Step 2: Standard method: add the other loads

LoadRuleVA
General loadsTable 220.425,625
Fixed appliances (fewer than 4)220.53 — 100%4,500
Range, 10 kWTable 220.55 Column C8,000
Dryer220.54 — 5,000 VA minimum5,000
Heating (larger than cooling)220.6010,000
Total33,125

Step 3: Optional method (220.82)

All general loads and appliances at nameplate: 10,500 + 4,500 + 10,000 (range) + 5,000 (dryer) = 30,000 VA. The first 10 kVA at 100% and the rest at 40% gives 18,000 VA. The heat pump is added at 100% under 220.82(C).

Result summary

CheckRequirementActualStatus
Standard methodn/a33,125 VA → 150 A✓ PASS
Optional methodn/a28,000 VA → 125 A✓ PASS
The optional method allows a 125 A service, the standard method 150 A. Either is code-compliant for a single dwelling; many designers still choose 200 A for future loads such as an EV charger.

Key insight: The optional method's single 40% factor above 10 kVA is more generous than the separate standard-method factors, which is why it usually gives a smaller service for a typical house.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open NEC 220 Residential Electrical Load Calculator calculator →