A 2,000 ft² house works out at 150 A by the standard method but 125 A by the optional method — here is where the difference comes from.
| Floor area | 2,000 ft² |
| Small-appliance and laundry circuits | 2 × 1,500 VA and 1 × 1,500 VA |
| Other fixed appliances | 3 appliances totalling 4,500 VA |
| Range and dryer | 10 kW range, 5,000 VA dryer |
| HVAC | 4,800 VA cooling, 10,000 VA heat pump heating (larger of the two used) |
| Supply | 240 V single-phase |
| Load | Rule | VA |
|---|---|---|
| General loads | Table 220.42 | 5,625 |
| Fixed appliances (fewer than 4) | 220.53 — 100% | 4,500 |
| Range, 10 kW | Table 220.55 Column C | 8,000 |
| Dryer | 220.54 — 5,000 VA minimum | 5,000 |
| Heating (larger than cooling) | 220.60 | 10,000 |
| Total | 33,125 |
All general loads and appliances at nameplate: 10,500 + 4,500 + 10,000 (range) + 5,000 (dryer) = 30,000 VA. The first 10 kVA at 100% and the rest at 40% gives 18,000 VA. The heat pump is added at 100% under 220.82(C).
| Check | Requirement | Actual | Status |
|---|---|---|---|
| Standard method | n/a | 33,125 VA → 150 A | ✓ PASS |
| Optional method | n/a | 28,000 VA → 125 A | ✓ PASS |
Key insight: The optional method's single 40% factor above 10 kVA is more generous than the separate standard-method factors, which is why it usually gives a smaller service for a typical house.
Every input in this example is editable in the live calculator — no signup needed.
Open NEC 220 Residential Electrical Load Calculator calculator →NEC 220.57 counts EVSE at 7,200 VA or its nameplate rating, whichever is larger. A 7,680 VA (32 A) charger would add 7,680 VA in the standard method.