🎉 Free launch period — every calculator, every feature unlocked, no account needed, through mid-November 2026. PDF reports carry a watermark for everyone during this period.
IEC 60255-1518 min read

Worked Example: Earth Fault Relay Trip Time with a Dual-Stage (50N/51N) Scheme

An earth-fault relay with both an inverse-time (51N) stage and a high-set instantaneous (50N) stage, checked at two different fault levels.

Scenario

Relay pickup (Ie>)0.2 A (relay/secondary side)
CT ratio200 : 1
Time multiplier (TMS)0.2, IEC Standard Inverse (SI)
Instantaneous stage (Ie>>)4000 A primary, 0.05 s definite-time delay
Case A — primary earth fault current1500 A
Case B — primary earth fault current5000 A

Step-by-step calculation

Step 1: Refer the primary fault current to the relay side via the CT ratio

Ie = Ifault(primary) / CT ratio
Case A: Ie = 1500 / 200 = 7.5 A Case B: Ie = 5000 / 200 = 25 A
Case A: 7.5 A, Case B: 25 A

Step 2: Compute the plug setting multiplier (PSM)

PSM = Ie / pickup
Case A: PSM = 7.5 / 0.2 = 37.5 Case B: PSM = 25 / 0.2 = 125
Case A: PSM = 37.5, Case B: PSM = 125

Step 3: Apply the IEC SI curve for the inverse-time (51N) stage

t = TMS x (0.14 / (PSM^0.02 - 1))
Case A: t = 0.2 x (0.14 / (37.5^0.02 - 1)) = 0.372 s Case B: t = 0.2 x (0.14 / (125^0.02 - 1)) = 0.276 s
Case A: 0.372 s, Case B: 0.276 s

Step 4: Check whether the fault exceeds the instantaneous (50N) pickup

The high-set instantaneous stage bypasses the inverse-time curve entirely for severe faults, tripping on a short fixed delay instead.

CasePrimary fault current50N pickupInstantaneous stage
A1500 A4000 ARestrained — below pickup
B5000 A4000 AOperates in 0.05 s (definite time)

Result summary

CheckRequirementActualStatus
Case A (1500 A) — governing trip pathn/a51N inverse-time stage, 0.372 s✓ PASS
Case B (5000 A) — governing trip pathn/a50N instantaneous stage, 0.05 s (bypasses the 0.276 s IDMT time)✓ PASS
At 1500 A the relay clears the fault on its inverse-time curve in 0.372 s. At 5000 A the instantaneous stage takes over and clears it in 0.05 s — roughly 5x faster — because the fault now exceeds the 4000 A high-set pickup.

Key insight: A dual-stage scheme gives you both worlds: the inverse-time stage keeps grading margin with downstream/upstream devices for moderate faults, while the instantaneous stage clears severe, close-in faults almost immediately, since there's no coordination need at currents that high — nothing downstream should still be carrying that much fault current.

Try it with your own numbers

Every input in this example is editable in the live calculator — free, no signup.

Open IDMT Earth Fault Relay (50N/51N) calculator →

Frequently asked questions

Why not just set the instantaneous stage very low and skip the inverse-time curve entirely?

An instantaneous stage set too low would trip for faults further down the network that a downstream device should clear first, defeating coordination. The high-set pickup is deliberately set above any fault level the relay should see from a downstream fault, so it only operates for faults close to the relay itself.

What does PSM mean physically?

The plug setting multiplier is simply how many times over pickup the relay is currently seeing. A PSM of 1.0 is right at the trip threshold (technically never trips, since the curve is asymptotic there); higher PSM means a more severe fault and a faster trip time.

More in Protection & Relaying

← Back to all worked examples