IEEE Std 142 ring formula6 min read

Worked Example: Can a Perimeter Ring Electrode Reach 10 Ω in 200 Ω·m Soil?

A buried ring around a small building, checked against the 10 Ω usually aimed for in lightning protection earthing. A 12 m ring falls short; a 20 m ring passes.

Scenario

Soil resistivity200 Ω·m (measured, Wenner method)
ConductorBare copper, 10 mm diameter
Burial depth0.6 m
Target10 Ω (low-frequency earth resistance aimed for in BS EN 62305-3)
OptionsRing of 12 m diameter (close to the building) or 20 m diameter (around the site)

BS 7430:2011 does not give a ring formula, so the ring-of-wire formula from IEEE Std 142 (Dwight) is used, with s equal to twice the burial depth.

Step-by-step calculation

Step 1: Ring formula

D is the ring diameter, d the conductor diameter and h the burial depth.

R = ρ / (2π²D) × [ln(8D/d) + ln(4D/s)], s = 2h

Step 2: 12 m ring

Step 3: 20 m ring

Step 4: Other ways to lower the resistance

Instead of a larger ring, earth rods can be added to the 12 m ring, driven deep where the soil is wetter. The conductor size has only a small effect: doubling the diameter lowers the 12 m ring by about 0.6 Ω.

Result summary

CheckRequirementActualStatus
12 m ring≤ 10 Ω10.86 Ω✗ FAIL
20 m ring≤ 10 Ω7.03 Ω✓ PASS
In 200 Ω·m soil a 12 m ring gives about 10.9 Ω and misses the 10 Ω target; a 20 m ring gives 7.0 Ω and meets it. Confirm the installed value with a fall-of-potential test.

Key insight: Ring resistance falls roughly in inverse proportion to the ring diameter. Size matters far more than conductor thickness.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open Ground Ring Resistance Calculator calculator →

Frequently asked questions

Why not use BS 7430 for the ring?

BS 7430:2011 gives formulas for rods, plates, straight strips, meshes and some star and cruciform layouts, but not for a ring. IEEE Std 142's ring-of-wire formula is the usual reference.

Is the 10 Ω target mandatory?

BS EN 62305-3 recommends a low earth resistance, if possible below 10 Ω, for a lightning protection earth. Electrical safety requirements for the installation are set separately, for example by disconnection times and touch voltages.