BS 7430:2011+A1 9.77 min read

Earthing Conductor Size for a 25 kA Fault: Bolted vs Welded Joints (BS 7430)

Part 5 of the earthing series. The joint type sets the maximum temperature, and the maximum temperature sets the conductor size: 142 mm² with bolted joints, 113 mm² with welded joints.

Scenario

Fault current25 kA, through the earthing conductor
Duration1 s (back-up protection clearing time)
MaterialBare copper, initial temperature 30 °C

Step-by-step calculation

Step 1: Current density for the final temperature

k = K × √ln((Tm + β)/(Ti + β)), copper K = 226, β = 234.5
Bolted joints, Tm = 250 °C: k = 226 × √ln(484.5/264.5); welded, Tm = 450 °C: k = 226 × √ln(684.5/264.5)
k = 176 A/mm² (bolted); k = 220 A/mm² (welded) — matching BS 7430 Table 4

Step 2: Minimum cross-section

S = I × √t / k
Bolted: 25,000 × 1 / 176; welded: 25,000 × 1 / 220
S = 142 mm² (bolted) → 150 mm²; S = 113 mm² (welded) → 120 mm²

Step 3: Galvanised steel for comparison

Steel: K = 78, β = 202; the zinc coating limits the temperature.

Step 4: Which duration?

Use the back-up protection clearing time, not the primary relay time, because the conductor must survive if the main protection fails. A 0.5 s duration would reduce the bolted-joint size to 101 mm².

Result summary

CheckRequirementActualStatus
Bolted joints (250 °C)S ≥ 142 mm²150 mm² selected✓ PASS
Welded joints (450 °C)S ≥ 113 mm²120 mm² selected✓ PASS
For 25 kA for 1 s, a bare copper earthing conductor needs 142 mm² with bolted joints (use 150 mm²) or 113 mm² with welded joints (use 120 mm²).

Key insight: The weakest point is the joint, not the conductor. Sizing with a high k (welded) while installing bolted clamps under-sizes the conductor by about 25 %.

Try it with your own numbers

Every input in this example is editable in the live calculator — no signup needed.

Open Earthing Grid Design (IEEE 80) calculator →

Frequently asked questions

Should the full fault current or the grid current IG be used?

The full fault current that can flow in the conductor. IG is only the part that flows into the soil and is used for GPR and touch voltages.

Is mechanical strength also a limit?

Yes. BS 7430 gives minimum sizes for buried conductors regardless of fault current, for example 25 mm² copper without corrosion protection.