🎉 Free launch period — every calculator, every feature unlocked, no account needed, through mid-November 2026. PDF reports carry a watermark for everyone during this period.
NEC 210.19/215.2 + 240.4, NEC 430.5210 min read

Worked Example: OCPD Sizing for a General Load and a Motor Circuit per NEC

Two different sizing rules in the same calculator — a general continuous/non-continuous load, and a motor branch circuit sized for starting-current withstand instead of running current.

Scenario

General load — continuous80 A
General load — non-continuous20 A
Cable ampacity (Iz)130 A
Motor full-load current (FLC)34 A
Motor category"Other" (NEC Table 430.52(C)(1))
OCPD type (motor path)Time-delay fuse

Step-by-step calculation

Step 1: General load — compute the minimum OCPD rating

NEC 210.19(A)(1)/215.2(A)(1) require 125% of continuous load plus 100% of non-continuous load.

minOCPD = 1.25 x Icontinuous + 1.0 x Inon-continuous
minOCPD = 1.25 x 80 + 1.0 x 20 = 100 + 20
minOCPD = 120 A

Step 2: Round up to the next standard NEC 240.6(A) size

Step 3: Verify the cable is protected (NEC 240.4)

Recommended OCPD ≤ cable ampacity Iz?
125 A ≤ 130 A
Yes — cable is directly protected, no exception needed

Step 4: Motor circuit — compute the OCPD from FLC, not running current

NEC 430.52(C)(1) sizes the branch-circuit OCPD as a percentage of motor full-load current to survive inrush/starting current, not steady-state running current. "Other" motors on a time-delay fuse use 175%.

minOCPD = 175% x FLC
minOCPD = 1.75 x 34 = 59.5 A
minOCPD = 59.5 A -> rounds up to 60 A

Step 5: Find the 430.52(C)(1)(b) exception ceiling, in case 60 A can't start the motor

If the standard 175% size genuinely can't carry the motor's starting current without nuisance tripping, the exception permits going up to 225% for a time-delay fuse — but only as high as needed, and rounded down to the nearest standard size.

exceptionCeiling = 225% x FLC, rounded down to standard size
225% x 34 = 76.5 A -> rounds down to 70 A
Exception ceiling = 70 A

Result summary

CheckRequirementActualStatus
General load OCPD protects the cableOCPD ≤ Iz125 A ≤ 130 A✓ PASS
Motor branch OCPD within NEC 430.52 window60 A – 70 A (standard to exception ceiling)60 A recommended✓ PASS
The general load circuit is protected at 125 A. The motor branch circuit's standard OCPD is 60 A (175% of FLC), with headroom up to 70 A available under the 430.52(C)(1)(b) exception if the motor's starting current trips a 60 A time-delay fuse.

Key insight: Motor branch-circuit protection is deliberately sized off starting-current withstand (via a percentage of FLC), not the general continuous-load rule — a motor's running current is far below its OCPD rating by design, because the device has to ride through several seconds of inrush at 5-8x FLC without tripping.

Try it with your own numbers

Every input in this example is editable in the live calculator — free, no signup.

Open Circuit Breaker & Fuse Sizer calculator →

Frequently asked questions

Why is the motor OCPD (60 A) so much higher than its running current (34 A) but the general load OCPD is much closer to its load?

A motor's OCPD has to survive its own starting current — typically several times FLC for a few seconds during across-the-line starting — without tripping, which is why NEC 430.52 permits sizing it well above running current. A general load's OCPD only has to cover normal continuous operation with a duty-cycle margin, so it stays much closer to actual load.

What happens if the cable ampacity is below the recommended OCPD?

NEC 240.4(B) allows using the next higher standard OCPD size than the cable's ampacity in specific circumstances (generally up to 800 A, and only where the ampacity doesn't itself correspond to a standard size) — but if that exception doesn't apply, the cable must be upsized instead of oversizing the protective device beyond what the conductor can safely carry.

More in Protection & Relaying

← Back to all worked examples