With a process bus, the protection relay no longer sees the CT and VT wiring — only the sampled values. Wrong channel mapping, a swapped phase, a neutral CT with the wrong polarity, lost samples or an unsynchronised merging unit look correct in the configuration and wrong only in the samples. Plotting the samples and computing the phasors shows it immediately, before secondary injection testing.
Standards followed
IEC 61850-9-2 and the UCA 9-2LE implementation guideline (80 samples per cycle, 4 currents + 4 voltages, 1 mA / 10 mV per bit)IEC 61869-9 (digital interface of instrument transformers)IEC 61850-7-3 quality; smpSynch (0 none, 1 local, 2 global)
What it can do
- Decodes sampled-value frames (APPID, svID, smpCnt, confRev, smpSynch, eight values with quality) and groups them per stream.
- Plots two cycles of currents and voltages from any sample, and shows phasors (RMS magnitude and angle relative to Va), frequency from the phase advance between two cycles, and positive, negative and zero sequence.
- Checks: lost samples (smpCnt gaps, counter wrapping at the samples per second), smpSynch, simulation, quality per channel, neutral current against Ia + Ib + Ic sample by sample, phase sequence, current and voltage unbalance, zero-sequence voltage, frequency.
Example problem
The demonstration capture: a 9-2LE merging unit at 80 samples per cycle, 50 Hz.
- Phasors: 70.7 A per phase 120° apart, 44.9 kV per phase; frequency 50.00 Hz.
- 8 samples are missing at one place.
- At sample 1506 the neutral channel reads 40 A while the three phases sum to zero.
Lost samples and a faulty neutral channel — both found before the relay is tested.
Scaling follows 9-2LE (1 mA, 10 mV per bit); IEC 61869-9 streams with other scaling show proportional values. Capture at the relay's process-bus port. Files are read in your browser.