Power Quality & Energy File Analyser
Two analyses from the files meters and power-quality analysers export: maximum demand, load factor and profiles from an interval load profile; and EN 50160 compliance (voltage, harmonics, flicker, unbalance, frequency) from a week of 10-minute values.
Load profile
Result
Open a load profile or load the sample.
What this tool is, how it works and how far to trust it
An analyser for meter and PQ analyser exports: maximum demand and load factor from a load profile, and EN 50160 compliance from a week of 10-minute values.
Read this before relying on a result. Every method, formula, assumption and limit is stated here, so you can check the answer yourself instead of accepting it blindly.
What it can do
- Load profile: read kW per interval, kWh per interval or cumulative kWh; compute maximum block demand (15/30/60 min), average, load factor, energy, daily maxima, 24-hour average profile, top 10 peaks and peak / off-peak energy.
- Power quality: read phase voltages, THDu, Pst/Plt, unbalance and frequency; compute EN 50160 compliance per parameter with percentiles and extremes; count values below 90 % of Un.
Why you need it
- Demand charges are set by a handful of peaks; knowing when and why they happen is the cheapest saving.
- Power-quality complaints are settled against EN 50160 over a full week, with percentiles that are easy to get wrong by hand.
Understand this first
- Maximum demand is the highest average over the tariff's integration period, not the highest instantaneous value.
- Load factor = average demand / maximum demand: a low value means short peaks that cost demand charges.
- EN 50160 sets limits for 95 % (or 99 %) of the 10-minute values of a week: e.g. THDu ≤ 8 %, Plt ≤ 1, unbalance ≤ 2 %, voltage within ±10 %.
What you need before you start
- A load profile export from the meter (CSV), ideally a full month.
- A week of 10-minute values from a PQ analyser (CSV) and the nominal voltage.
- A current browser (Chrome, Edge, Firefox or Safari). Nothing is installed and your data is never uploaded; it is processed on your own computer.
How to use it
- Choose the tab, open the file (or load the sample) and set the demand period or the nominal voltage and network level.
- Read the KPIs and findings, then the profile, peaks or the parameter table.
- For a failing PQ parameter, note the time pattern of the worst values and measure the suspected loads.
What you get
- Load: maximum demand with time, average, load factor, energy, findings, hourly profile and top peaks.
- PQ: compliance per parameter with limit, percentage within limit and extremes; findings.
How to read the results
- One day's peak well above the others: a coincidence of starts — staggering them cuts the demand charge.
- THDu failing in the evening only: a specific load (rectifiers, drives) — locate it with harmonic measurements per feeder.
- Plt failing on working days: a fluctuating load such as an arc furnace or welder.
Technical basis
- EN 50160; IEC 61000-4-30 10-minute aggregation; IEC 61000-4-15 flicker; tariff block-demand practice.
Limits: when not to rely on it
- EN 50160 frequency limits refer to 10-second values over a year; 10-minute values give an indication only.
- The tool reads the meter's values; it cannot correct for wrong CT/VT ratios or a meter set to the wrong integration period.
Sample files for this tool
Download, open and compare with what the guide says you should see.
- S13_J01_load_profile.csv — Industrial customer J01 — 30 days of 15-minute demand
- S13_33kV_PQ_week.csv — S13 33 kV busbar — one week of 10-minute PQ values
For preliminary engineering use. Results must be checked by a qualified engineer against the project's standards. How results are checked · Terms & disclaimer · Privacy · Build 7cfcbe2 · 2026-11-14