UPS Sizing Calculator

Required UPS kVA rating from critical load, margin, and redundancy configuration, plus an approximate battery energy/Ah figure for the stated backup time. For a full IEEE 485 duty-cycle battery design, see the Battery & DC System Sizing calculator. Fully free โ€” no subscriber gate.

AAJappsEngineering Calculation Report

UPS Sizing Calculator

IEEE 485-referenced, N-unit redundancy

Generated

For preliminary engineering use only โ€” always verify results against project-specific standards and a qualified engineer's review before use in a real design.

Critical load

kW
%

With N total UPS frames installed, any (Nโˆ’1) must be able to carry the full critical load alone (the same convention as the Transformer Sizer, commonly called โ€œN+1โ€ in UPS terminology) โ€” N=2 sizes each frame for 100% of the load.

Battery / backup time

min
V

UPS sizing result

Design Load222.2 kVA
Margined Load266.7 kVA
Per-Unit Required (รท1)266.7 kVA
Recommended Standard Size300 kVA per unit
Capability at Rated PF270.0 kW

Approximate battery requirement

Usable Energy50.00 kWh
Nameplate Battery Energy67.93 kWh
Approx. Capacity at DC Bus Voltage141.5 Ah