Sizes an off-grid PV charge controller's required continuous current rating. PWM controllers track close to the array's short-circuit current, so sizing is based directly on Isc ร parallel strings. MPPT controllers regulate power on the DC bus and draw current based on power balance, so sizing is based on array maximum power รท nominal battery voltage. Both paths apply the standard NEC 690.8(A) 125% continuous-current factor plus a user-settable design margin.
Standards followed
NEC 690.8(A) โ 125% continuous-current factor for PV source/output circuits
What it can do
- PWM path: controller current from array Isc ร parallel strings.
- MPPT path: controller current from array max power รท nominal battery voltage.
- 125% continuous factor plus an additional user-settable design margin.
- Rounds up to a commonly available charge controller current rating (practical reference, not an official standard series).
Example problem
MPPT controller, 4000W array, 48V nominal battery, 10% additional design margin.
- Base current = 4000/48 โ 83.33A
- Required rating = 83.33 ร 1.25 ร 1.10 โ 114.6A
โ114.6A required โ 150A commonly available controller recommended.
MPPT controller current draw varies with array operating point and battery state of charge โ this is a first-pass sizing estimate based on rated array power, not a full I-V curve tracking simulation. Always confirm against the specific controller manufacturer's maximum PV input voltage/power and battery-side current limits.