Emergency Lighting Duration Calculator

Check an existing battery/unit-equipment runtime against the common 90-minute code minimum, or size the required battery capacity for a target duration with aging, DoD and inverter-efficiency derating.

AAJappsEngineering Calculation Report

Emergency Lighting Duration Calculator

NFPA 101 §7.9.2.1 / NEC 700.12(F) — 90-minute common minimum duration

Generated

For preliminary engineering use only — always verify results against project-specific standards and a qualified engineer's review before use in a real design.

Mode

Load & battery

W
Wh
%
%

Runtime check

Runtime77.8 min
GradeBELOW MINIMUM
vs. 90-min referenceBelow minimum ✗