 "format": "SCL NetStudio project",
 "v": 1,
 "name": "S13 132/33 kV Substation",
 "ieds": [
  {
   "name": "GW1",
   "desc": "Station gateway (IEC 104 to control centre)",
   "bay": "Station",
   "role": "gateway",
   "nets": {
    "sb": 1,
    "dmz": 1
   },
   "sw": "SW2",
   "swp": "",
   "ips": {
    "sb": "10.13.0.11",
    "dmz": "10.13.1.11"
   },
   "asset": {
    "panel": "+S01",
    "mfr": "Vendor C",
    "model": "SG-4000",
    "fw": "5.1.2",
    "serial": "C4K-21-0381",
    "mac": "02-AA-00-00-01-01",
    "status": "planned"
   }
  },
  {
   "name": "HMI1",
   "desc": "Station HMI",
   "bay": "Station",
   "role": "hmi",
   "nets": {
    "sb": 1
   },
   "sw": "SW2",
   "swp": "",
   "ips": {
    "sb": "10.13.0.12"
   },
   "asset": {
    "panel": "+S02",
    "mfr": "Vendor D",
    "model": "Station PC",
    "fw": "2021 LTSC",
    "serial": "SPC-77120",
    "mac": "02-AA-00-00-01-02",
    "status": "planned"
   }
  },
  {
   "name": "GPS1",
   "desc": "GPS master clock (PTP grandmaster)",
   "bay": "Station",
   "role": "clock",
   "nets": {
    "sb": 1,
    "pb": 1,
    "mg": 1
   },
   "sw": "SW2",
   "swp": "PB1",
   "ips": {
    "sb": "10.13.0.13",
    "pb": "10.13.0.139",
    "mg": "10.13.0.197"
   },
   "asset": {
    "panel": "+S01",
    "mfr": "Vendor E",
    "model": "TS-2",
    "fw": "4.3",
    "serial": "TS2-008815",
    "mac": "02-AA-00-00-01-03",
    "status": "planned"
   }
  },
  {
   "name": "P132_Q01",
   "desc": "Line 1 distance protection",
   "bay": "Q01",
   "role": "protection",
   "nets": {
    "sb": 1,
    "pb": 1
   },
   "sw": "SW1",
   "swp": "PB1",
   "ips": {
    "sb": "10.13.0.14",
    "pb": "10.13.0.140"
   },
   "asset": {
    "panel": "+R01",
    "mfr": "Vendor A",
    "model": "DP-700",
    "fw": "3.2.1",
    "serial": "A7-1904411",
    "mac": "02-AA-00-00-02-01",
    "status": "planned"
   }
  },
  {
   "name": "P132_Q02",
   "desc": "Line 2 distance protection",
   "bay": "Q02",
   "role": "protection",
   "nets": {
    "sb": 1
   },
   "sw": "SW1",
   "swp": "",
   "ips": {
    "sb": "10.13.0.15"
   },
   "asset": {
    "panel": "+R02",
    "mfr": "Vendor A",
    "model": "DP-700",
    "fw": "3.1.4",
    "serial": "A7-1904412",
    "mac": "02-AA-00-00-02-02",
    "status": "planned"
   }
  },
  {
   "name": "P87T_T1",
   "desc": "T1 differential protection",
   "bay": "Q03",
   "role": "protection",
   "nets": {
    "sb": 1,
    "pb": 1
   },
   "sw": "SW1",
   "swp": "PB1",
   "ips": {
    "sb": "10.13.0.16",
    "pb": "10.13.0.141"
   },
   "asset": {
    "panel": "+R03",
    "mfr": "Vendor A",
    "model": "TD-500",
    "fw": "3.2.1",
    "serial": "A5-2001876",
    "mac": "02-AA-00-00-02-03",
    "status": "planned"
   }
  },
  {
   "name": "BCU_J01",
   "desc": "33 kV incomer bay controller",
   "bay": "J01",
   "role": "control",
   "nets": {
    "sb": 1
   },
   "sw": "SW2",
   "swp": "",
   "ips": {
    "sb": "10.13.0.17"
   },
   "asset": {
    "panel": "+J01",
    "mfr": "Vendor B",
    "model": "BC-300",
    "fw": "2.0.8",
    "serial": "B3-118204",
    "mac": "02-AA-00-00-03-01",
    "status": "planned"
   }
  },
  {
   "name": "MU_Q01",
   "desc": "Line 1 merging unit",
   "bay": "Q01",
   "role": "mu",
   "nets": {
    "pb": 1
   },
   "sw": "",
   "swp": "PB1",
   "ips": {
    "pb": "10.13.0.142"
   },
   "asset": {
    "panel": "=Q01+K1",
    "mfr": "Vendor B",
    "model": "MU-90",
    "fw": "1.4.0",
    "serial": "",
    "mac": "02-AA-00-00-04-01",
    "status": "planned"
   }
  },
  {
   "name": "MU_T1",
   "desc": "T1 HV merging unit",
   "bay": "Q03",
   "role": "mu",
   "nets": {
    "pb": 1
   },
   "sw": "",
   "swp": "PB1",
   "ips": {
    "pb": "10.13.0.143"
   },
   "asset": {
    "panel": "=Q03+K1",
    "mfr": "Vendor B",
    "model": "MU-90",
    "fw": "1.4.0",
    "serial": "B9-220190",
    "mac": "02-AA-00-00-04-02",
    "status": "planned"
   }
  }
 ],
 "switches": [
  {
   "name": "SW1",
   "bus": "sb",
   "speed": 100,
   "uplink": 1000,
   "desc": "Station bus · 132 kV bays",
   "ip": "10.13.0.194",
   "ports": 8,
   "asset": {
    "panel": "+S03",
    "mfr": "Vendor F",
    "model": "RSW-8",
    "fw": "6.2",
    "serial": "RS8-40551",
    "mac": "02-AA-00-00-0F-01",
    "status": "planned"
   }
  },
  {
   "name": "SW2",
   "bus": "sb",
   "speed": 100,
   "uplink": 1000,
   "desc": "Station bus · station level and 33 kV",
   "ip": "10.13.0.195",
   "ports": 8,
   "asset": {
    "panel": "+S03",
    "mfr": "Vendor F",
    "model": "RSW-8",
    "fw": "6.2",
    "serial": "RS8-40552",
    "mac": "02-AA-00-00-0F-02",
    "status": "planned"
   }
  },
  {
   "name": "PB1",
   "bus": "pb",
   "speed": 100,
   "uplink": 1000,
   "desc": "Process bus",
   "ip": "10.13.0.196",
   "ports": 8,
   "asset": {
    "panel": "+S04",
    "mfr": "Vendor F",
    "model": "RSW-8",
    "fw": "6.2",
    "serial": "RS8-40553",
    "mac": "02-AA-00-00-0F-03",
    "status": "planned"
   }
  }
 ],
 "arch": "star",
 "ip": {
  "block": "10.13.0.0/22",
  "gwPos": "first",
  "reserve": 9,
  "segs": [
   {
    "name": "Station bus",
    "role": "sb",
    "hosts": 60,
    "growth": 50
   },
   {
    "name": "Process bus",
    "role": "pb",
    "hosts": 24,
    "growth": 50
   },
   {
    "name": "Management",
    "role": "mg",
    "hosts": 20,
    "growth": 50
   },
   {
    "name": "SCADA DMZ",
    "role": "dmz",
    "hosts": 6,
    "growth": 100
   },
   {
    "name": "Engineering",
    "role": "eng",
    "hosts": 10,
    "growth": 50
   }
  ]
 },
 "streams": [
  {
   "type": "GOOSE",
   "pub": "P132_Q01",
   "ld": "PROT",
   "cb": "GCB_TRIP",
   "datSet": "DS_TRIP",
   "members": 4,
   "trip": true,
   "subs": [
    "P87T_T1",
    "BCU_J01"
   ],
   "confRev": 1,
   "mac": "01-0C-CD-01-00-01",
   "appid": "0001",
   "vlan": 10,
   "prio": 6,
   "minT": 4,
   "maxT": 1000
  },
  {
   "type": "GOOSE",
   "pub": "P132_Q02",
   "ld": "PROT",
   "cb": "GCB_TRIP",
   "datSet": "DS_TRIP",
   "members": 4,
   "trip": true,
   "subs": [
    "P87T_T1"
   ],
   "confRev": 1,
   "mac": "01-0C-CD-01-00-02",
   "appid": "0002",
   "vlan": 10,
   "prio": 6,
   "minT": 4,
   "maxT": 1000
  },
  {
   "type": "GOOSE",
   "pub": "P87T_T1",
   "ld": "PROT",
   "cb": "GCB_DIFF",
   "datSet": "DS_DIFF",
   "members": 6,
   "trip": true,
   "subs": [
    "P132_Q01",
    "P132_Q02",
    "BCU_J01"
   ],
   "confRev": 1,
   "mac": "01-0C-CD-01-00-03",
   "appid": "0003",
   "vlan": 10,
   "prio": 6,
   "minT": 4,
   "maxT": 1000
  },
  {
   "type": "GOOSE",
   "pub": "BCU_J01",
   "ld": "CTRL",
   "cb": "GCB_IL",
   "datSet": "DS_ILOCK",
   "members": 8,
   "trip": false,
   "subs": [
    "P132_Q01",
    "P132_Q02"
   ],
   "confRev": 1,
   "mac": "01-0C-CD-01-00-04",
   "appid": "0004",
   "vlan": 10,
   "prio": 4,
   "minT": 4,
   "maxT": 1000
  },
  {
   "type": "SV",
   "pub": "MU_Q01",
   "ld": "MU",
   "cb": "MSVCB01",
   "datSet": "PhsMeas1",
   "members": 8,
   "smpRate": 80,
   "nofASDU": 1,
   "subs": [
    "P132_Q01"
   ],
   "confRev": 1,
   "mac": "01-0C-CD-04-00-01",
   "appid": "4001",
   "vlan": 11,
   "prio": 4
  },
  {
   "type": "SV",
   "pub": "MU_T1",
   "ld": "MU",
   "cb": "MSVCB01",
   "datSet": "PhsMeas1",
   "members": 8,
   "smpRate": 80,
   "nofASDU": 1,
   "subs": [
    "P87T_T1"
   ],
   "confRev": 1,
   "mac": "01-0C-CD-04-00-02",
   "appid": "4002",
   "vlan": 11,
   "prio": 4
  }
 ],
 "vr": {
  "scheme": "type",
  "gV": 10,
  "svV": 11,
  "gP": 4,
  "tripP": 6,
  "svP": 4,
  "gMin": 4,
  "gMax": 1000,
  "keep": false,
  "dataVlan": 1,
  "member": "subs"
 },
 "bw": {
  "f": 50,
  "filter": "vlan",
  "mms": 64,
  "avalanche": true
 },
 "lat": {
  "stream": 0,
  "hops": 3,
  "acc": 100,
  "bb": 1000,
  "swLat": 5,
  "mode": "sf",
  "interf": true,
  "ahead": 2,
  "cable": 300,
  "ta": 1,
  "tc": 1,
  "cls": "1A23"
 },
 "red": {
  "n": 12,
  "speed": 100,
  "node": 5,
  "frame": 160,
  "traffic": 0,
  "budget": 1,
  "prpDan": 8,
  "prpSan": 2
 },
 "ts": {
  "use": "sv_prot",
  "method": "ptp",
  "gm": 250,
  "tc": 4,
  "tcErr": 50,
  "bc": 0,
  "bcErr": 200,
  "end": 200,
  "sntp": 1000,
  "irigLen": 150,
  "osc": "tcxo",
  "rss": false
 },
 "fw": {
  "zones": [
   {
    "id": "cc",
    "name": "Control centre (SCADA)",
    "sl": 2
   },
   {
    "id": "dmz",
    "name": "Substation DMZ",
    "sl": 3
   },
   {
    "id": "st",
    "name": "Station LAN",
    "sl": 3
   },
   {
    "id": "pb",
    "name": "Process bus",
    "sl": 3
   },
   {
    "id": "eng",
    "name": "Engineering / maintenance",
    "sl": 2
   },
   {
    "id": "it",
    "name": "Corporate IT",
    "sl": 1
   },
   {
    "id": "ven",
    "name": "Remote vendor access",
    "sl": 1
   },
   {
    "id": "ts",
    "name": "Time source (GPS)",
    "sl": 3
   }
  ],
  "rules": [
   {
    "from": "cc",
    "to": "dmz",
    "svc": "iec104tls",
    "note": "Telecontrol from the control centre to the gateway"
   },
   {
    "from": "dmz",
    "to": "st",
    "svc": "mms",
    "note": "Gateway reads IEDs through reports"
   },
   {
    "from": "eng",
    "to": "st",
    "svc": "mms",
    "note": "Engineering tools: settings, disturbance records"
   },
   {
    "from": "eng",
    "to": "st",
    "svc": "https",
    "note": "IED web interfaces"
   },
   {
    "from": "eng",
    "to": "st",
    "svc": "ssh",
    "note": "Switch management"
   },
   {
    "from": "st",
    "to": "ts",
    "svc": "ntp",
    "note": "SNTP for devices without PTP"
   },
   {
    "from": "st",
    "to": "pb",
    "svc": "goose",
    "note": "Trip and interlocking between bays"
   },
   {
    "from": "it",
    "to": "st",
    "svc": "rdp",
    "note": "Corporate users want HMI access"
   },
   {
    "from": "ven",
    "to": "dmz",
    "svc": "vpn",
    "note": "Vendor support into the jump host"
   },
   {
    "from": "st",
    "to": "eng",
    "svc": "syslog",
    "note": "Security event logging"
   }
  ]
 },
 "cab": {
  "prefix": "NC",
  "cu": "Cat6A S/FTP, RJ45",
  "mm": "OM3 2-fibre, LC duplex",
  "sm": "OS2 2-fibre, LC duplex",
  "cuLen": 15,
  "fLen": 60,
  "upLen": 30,
  "upMedia": "mm",
  "trunkCores": 12
 },
 "lk": {
  "BCU_J01~sb": {
   "len": 115
  },
  "MU_Q01~pb": {
   "len": 180,
   "trunk": "FT-YARD-01",
   "ppA": "=Q01+K1",
   "ppB": "ODF-1"
  },
  "MU_T1~pb": {
   "len": 220,
   "trunk": "FT-YARD-01",
   "ppA": "=Q03+K1",
   "ppB": "ODF-1"
  }
 }
}